| 2001-09-25 00:00:00 | *******************DENIED*************** |
| | |
| | |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR REVIEW. |
| | |
| | 1.PLAN INDICATES CU-1A, CU-1B, CU-2A, |
| | CU-2B, AHU #1 AND #2.THE UNIT |
| | SCHEDULE INDICATES TWO AHU #1 AND |
| | TWO CU #1.IF SOME OF THE EQUIPMENT |
| | IS EXISTING PLEASE DISTINGUISH WHAT |
| | IS NEW AND WHAT MAY BE EXISTING. |
| | |
| | 2.DUCTS PENETRATING ONLY ONE FLOOR |
| | SHALL BE PROTECTED BY EITHER A SHAFT |
| | ENCLOSURE OF BY INSTALLING A LISTED |
| | FIRE DAMPER WHERE FLOOR IS PIERCED |
| | IN LIEU OF THE ENCLOSURE.1997 SMC |
| | 610.4.PLEASE INDICATE LOCATION OF |
| | FIRE DAMPERS AND ACCESS ON PLAN. |
| | |
| | 3.CONDENSATE LINES AND TERMINATION |
| | NEEDS TO BE ADDRESSED ON PLAN. |
| | NOTE, UNITS LARGER THAN 3 TON SHALL |
| | TERMINATE INTO STORM DRAIN OF TO AN |
| | APPROVED DRYWELL. AMENDED 1994 SPC |
| | 804.3 #2 AND 3. |
| | |
| | 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR |
| | WITH NOTIFICATION TO ALARM/STROBE IN |
| | NORMALLY OCCUPIED AREAS AS PER |
| | NFPA 90A 4-4.4.3. |
| | |