| Plan Review Notes For Permit 01090984 |
| Permit Number |
01090984 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-24 00:00:00 | 1) AN APPROVED FIXED TEMPERATURE | | | HEAT DETECTOR IS REQUIRED IN THE | | | ELEVATOR EQUIPMENT ROOM. THIS DEVICE | | | SHALL DISCONNECT THE POWER TO THE | | | ELEVATOR PRIOR TO THE APPLICATION OF | | | WATER. HEAT DETECTOR DOES NOT HAVE TO | | | BE CONNECTED TO THE BUILDINGS FIRE ALARM | | | SYSTEM. SYSTEM SHALL NOT AUTOMATICALLY | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|