| Plan Review Notes For Permit 01090908 |
| Permit Number |
01090908 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-12-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-FLOOD ZONE AO. NEED THE ELEVATION | | | CERTIFICATE. | | | 2-NEED ADDITIONAL SOIL BORINGS FOR EACH | | | STRUCTURE AS RECOMMENDED ON THE PRE- | | | LIMINARY SOIL TEST REPORT. | | | 3-PROVIDE PRODUCT APPROVAL FOR FRENCH | | | DOORS ASSEMBLIES AS SHOWN ON PLANS IF | | | OPTION SELECTED. | | | 4-PROVIDE MANUFACTURER'S CERTIFICATION | | | FOR TWO HOUR FIRE RATED CONCRETE BLOCK | | | ACCORDING TO THE BLOCK'S EQUIVALENT | | | THICKNESS AND AGGREGATES USED. SEE | | | SECTION 709.3 SBC 1997. | | | 5-PROVIDE COMPLETE INFORMATION FOR STORM | | | PANELS UNDER A SEPARATE PERMIT. | | | 6-TRUSS DRAWINGS: | | | -UPDATE ALL GENERAL TRUSS DETAILS. USE | | | ASCE 7-95 FOR 140 MPH, NOT ASCE 7-93. | | | SEE COMMENTS ON TRUSSES. | | | | | | | | | NOTES: | | | -DRAWINGS AND COMMENTS TO BE FILED UNDER | | | PERMIT #01090908. | | | -THESE COMMENTS APPLY TO PERMIT #S: | | | 01090908, 01090911, 01090914, 01090918, | | | 01090922 AND 01090924. |
|