| Plan Review Notes For Permit 01090882 |
| Permit Number |
01090882 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-26 00:00:00 | ********************DENIED************** | | | | | | | | | PLEASE PROVIDE MAKE, MODEL AND BTU'S | | | FOREQUIPMENT. | | | | | | AS PER FLORIDA ENERGY CODE SECTION | | | 101.4.1.1, ENERGY CALCULATIONS AS PER | | | CHAPTER6 SECTION 607.1.ABC.1, EQUIPMENT | | | SIZING CLCULATION SHALL BE PERFORMED ON | | | THE BUILDING AND SHALL BE ATTACHED TO | | | FORM 600 SUBMITTED WITH APPLICATION. | | | COOLING & HEATING DESIGN LOADS, FOR THE | | | PURPOSE OF SIZING HVAC SYSTEMS, SHALL | | | BE DETERMINED FOR EACH ZONE WITHIN A | | | DWELLING IN ACCORDANCE WIHHT ACCA | | | MANUAL J. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS 659-8096 EXT. 8388. |
|