| Plan Review Notes For Permit 01090788 |
| Permit Number |
01090788 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-10-17 00:00:00 | TRUSSES | | | UNSAT | | | | | | 1) TRUSS H7B (U=3913#) HAS AN UPLIFT | | | VALUE THAT EXCEEDS UPLIFT VALUE | | | SPECIFIED IN THE ANCHOR SCHEDULE (C2 U= | | | 2750#). PLEASE REVIEW AND CORRECT. | | | | | | 2) THE ANCHOR SCHEDULE DOES NOT SPECIFY | | | THE COMPLETE MODEL NUMBER OF THE | | | ANCHOR,SUCH AS HETA 12,16,20, ETC. | | | | | | 3) THERE IS A MARK A OPT. ON THE ROOF | | | FRAMING PLAN (SHEET3A), HOWEVER, THERE | | | IS NOT A CORRESPONDING MARK A IN THE | | | ANCHOR SCHEDULE. PLEASE CLARIFY. | | | | | | 4) THE TRUSS I.D. LABELS ON THE ON THE | | | TRUSS LAYOUT DO NOT CORRESPOND WITH THE | | | TRUSS DRAWINGS FOR SEVERAL OF THE | | | TRUSSES. T-11,T-11DS,H2710,ETC. | | | | | | 5) PLEASE INDICATE THE TRUSS THAT THE | | | C5 (2 PLY TRUSS HANGER) IS TO BE INSTALL | | | -ED ON. SEE TRUSS LAYOUT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|