| Plan Review Notes For Permit 01090788 |
| Permit Number |
01090788 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-17 00:00:00 | ************BUILDING PROVISO************ | | | | | | 1) PROVIDE ENGINEERED DETAIL OF ALUMINUM | | | COLUMN BASES AT COVERED PORCH INDICATING | | | METHOD OF ANCHORING. | | | | | | 2)PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - (UN-CLIPPED) TUBE MULLIONS (THE ONES | | | THAT WERE SUBMITTED EXPIRED ON 5/1/00) |
|