Plan Review Notes
Plan Review Notes For Permit 01090761
Permit Number 01090761
Review Stop P
Sequence Number 3
Notes
Date Text
2002-05-02 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SHT 5A SANITARY RISER DIAGRAM DOES
 NOT REFLECT FLOOR PLAN. "ODK" SHOULD BE
 TAKEN OFF BY POOL BATH AS ON FLOOR PLAN,
 NOT BY THE WASH MACHINE/LAUNDRY SINK AS
 SHOWN.
 2) WHAT IS "ODK" ?- WHAT IS "SW" LOOP
 BY DRAIN ADDED ON REVISION?
 3) SHT 5A BATH #3 SHOWER. ALL SHOWER
 COMPARTMENTS SHALL HAVE A MINIMUM OF 900
 SQUARE INCHES OF INTERIOR CROSS-SECTION-
 AL AREA. SHOWER COMPARTMENTS SHALL NOT
 BE LESS THAN 30 INCHES IN MINIMUM DIMEN-
 SION MEASURED FROM THE FINISHED INTERIOR
 DIMENSION OF THE COMPARTMENT.THE MINIMUM
 DIMENSION SHALL BE MEASURED AS THE SIDE
 OF A RECTANGLE, ALTITUDE OF A TRIANGLE,
 OR DIAMETER OF A CIRCLE.
  
 `EVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377