| Plan Review Notes For Permit 01090761 |
| Permit Number |
01090761 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-05-02 00:00:00 | DENIED | | | REFERENCE: SPC-94 | | | | | | 1) SHT 5A SANITARY RISER DIAGRAM DOES | | | NOT REFLECT FLOOR PLAN. "ODK" SHOULD BE | | | TAKEN OFF BY POOL BATH AS ON FLOOR PLAN, | | | NOT BY THE WASH MACHINE/LAUNDRY SINK AS | | | SHOWN. | | | 2) WHAT IS "ODK" ?- WHAT IS "SW" LOOP | | | BY DRAIN ADDED ON REVISION? | | | 3) SHT 5A BATH #3 SHOWER. ALL SHOWER | | | COMPARTMENTS SHALL HAVE A MINIMUM OF 900 | | | SQUARE INCHES OF INTERIOR CROSS-SECTION- | | | AL AREA. SHOWER COMPARTMENTS SHALL NOT | | | BE LESS THAN 30 INCHES IN MINIMUM DIMEN- | | | SION MEASURED FROM THE FINISHED INTERIOR | | | DIMENSION OF THE COMPARTMENT.THE MINIMUM | | | DIMENSION SHALL BE MEASURED AS THE SIDE | | | OF A RECTANGLE, ALTITUDE OF A TRIANGLE, | | | OR DIAMETER OF A CIRCLE. | | | | | | `EVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|