Plan Review Notes
Plan Review Notes For Permit 01090761
Permit Number 01090761
Review Stop E
Sequence Number 2
Notes
Date Text
2001-10-30 00:00:00**************** UNSAT*****************
  
 1)NOTE: PLEASE NOTE #1 FROM FIRST
 REVIEW,3-2/0`S FOR SINGLE PHASE
 SERVICE?PLEASE NOTE PLANS STILL SHOW A
 #1 CONDUCTOR? FOR ?
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3)NOTE: PLEASE NOTETHAT PLANS THAT
 ARE BACK IN MUST BE SIGNED,DATED AND
 SEALED BY THE ENGINEER OF RECORD.
 471.025 OF
 THE FS/FAC
  
 4) NOTE: PLEASE SHOW GROUNDING
 ELECTRODE GOING TO BUILDING STEEL AND
 COLD WATER PER 250-50.
  
 PLEASE NOTE :IS COLD WATER METAL? CPVC?
 PLEASE NOTE PER 250-50 .
  
 PLEASE NOTE MOST NOTES FROM FIRST
 REVIEW WERE ADDRESSED BUT STILL NEEDS
 SOME OTHERS DONE.
 PLEASE SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372