| Plan Review Notes For Permit 01090761 |
| Permit Number |
01090761 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-10-30 00:00:00 | **************** UNSAT***************** | | | | | | 1)NOTE: PLEASE NOTE #1 FROM FIRST | | | REVIEW,3-2/0`S FOR SINGLE PHASE | | | SERVICE?PLEASE NOTE PLANS STILL SHOW A | | | #1 CONDUCTOR? FOR ? | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 3)NOTE: PLEASE NOTETHAT PLANS THAT | | | ARE BACK IN MUST BE SIGNED,DATED AND | | | SEALED BY THE ENGINEER OF RECORD. | | | 471.025 OF | | | THE FS/FAC | | | | | | 4) NOTE: PLEASE SHOW GROUNDING | | | ELECTRODE GOING TO BUILDING STEEL AND | | | COLD WATER PER 250-50. | | | | | | PLEASE NOTE :IS COLD WATER METAL? CPVC? | | | PLEASE NOTE PER 250-50 . | | | | | | PLEASE NOTE MOST NOTES FROM FIRST | | | REVIEW WERE ADDRESSED BUT STILL NEEDS | | | SOME OTHERS DONE. | | | PLEASE SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|