Plan Review Notes
Plan Review Notes For Permit 01090761
Permit Number 01090761
Review Stop R
Sequence Number 1
Notes
Date Text
2001-10-05 00:00:00CHECKLIST:
 1-PROVIDE COMPLETE DETAIL/SECTION THRU
 STAIRWAY. SECTION 104.2.2OF CITY
 AMENDMENTS TO SBC 1997.
 2-PROVIDE ATTIC ACCESS.SEC 2309.6 SBC/97
 3-ENTRY DOOR TO HAVE 32" MIN. CLEAR
 OPENING. TABLE 1004 SBC 1997.
 4-SPECIFY FIREBLOCKING WHERE REQUIRED BY
 SEC. 2305 SBC/97.ALSO, SEE WALL SECT'N
 5-TRUSS COMPANY IS NOT LISTED IN THE
 PREFABRICATED WOOD COMPONENTS/TRUSS
 COMPLIANCE REPORT REPORTED TO THE
 BUILDING CODE ADVISORY BOARD OF PALM
 BEACH COUNTY. THEREFORE, TRUSSES WILL
 NOT BE APPROVED IN THIS COUNTY.
 6-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM. THE
 MEAN ROOF HEIGHT IS +/- 19'-0". THE
 MEAN ROOF HEIGHT IS TAKEN FROM THE
 FINISH GRADE, NOT FINISH FLOOR, TO THE
 AVERAGE POINT OF THE HIGHEST ROOF.
 7-SOIL TEST REPORT TO HAVE ENGINEER'S
 ORIGINAL SIGNATURE AS REQUIRED BY FL.
 STATUTES CHAPTER 471 WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 8-REVISE ENERGY CALCULATIONS SEE
 COMMENTS ON FIRST PAGE OF FORM 600A-97
 9-PROVIDE CURRENT SBCCI OR DADE COUNTY
 PRODUCT APPROVALS FOR:
 A)EXTERIOR DOORS AND WINDOWS. IF USING
 NORANDEX PRODUCTS, THEN THEY MUST BE
 SITE SPECIFIC AND SIGNED, SEALED AND
 DATED BY THE MANUFACTURER'S ENGINEER
 AND BY THE ENGINEER OF RECORD FOR THIS
 HOUSE.
 -CLEARLY INDICATE ON DRAWINGS THE
 FASTENERS TO BE USED FOR EACH WINDOW
 AND DOOR COMPLETE ASSEMBLY AS SHOWN ON
 ARCHITECTURAL PLANS ACCORDING TO THE
 DESIGN PRESSURES CALCULATED FOR THIS
 PROJECT.
 -SLIDING GLASS DOORS DON'T SHOW TEST
 PERFORMED AS PER ASTM E-330.
 B)WINDOW SILL ACTUAL PRODUCT APPROVAL.
 C)PRECAST LINTEL PRODUCT APPROVAL WAS
 DELETED BY SBCCI. NEED UPDATED ONE.
 D)GARAGE DOORS PRODUCT APPROVAL WAS
 DELETED BY SBCCI.
 E)ENTRY DOORS WITH SIDELITES AND TRANSOM
 ABOVE COMPLETE ASSEMBLY AS SHOWN ON
 ARCHITECTURAL PLANS.
  
 10-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS:
 -NEED KEY PLAN & COMPLETE INSTALLATION
 SCHEDULE, SEE CITY SAMPLE ATTACHED.
 -CLEARLY INDICATE ON STORM PANELS DWGS
 SPECIFIC MOUNTING CONDITIONS & ANCHORS
 TO BE USED ACCORDING TO THE MEAN ROOF
 HEIGHT, DESIGN PRESSURES, PANEL SPAN,
 EDGE DISTANCE, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO (MASONRY
 OR WOOD).
 11-PROVIDE SURVEY OR SITE PLAN SHOWING
 THE LAYOUT OF THE DRIVEWAY AND WALKWAY
 12-CONTRACTOR NEEDS TO UPDATE INSURANCE
 AND WORKER'S COMPENSATION.
 13-OWES $602.77 FOR UPDATED CONSTRUCTION
 VALUE AND RADON FEES. PLEASE PAY
 ATTACHED RECEIPT.
 14-SEE ADDITIONAL COMMENTS ON PLANS,
 INCLUDING COMMENTS BY OTHER TRADES.
 PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO THE ORIGINAL
 PLANS IN ORDER TO EXPEDITE THE REVIEW
 PROCESS.