Plan Review Notes
Plan Review Notes For Permit 01090761
Permit Number 01090761
Review Stop E
Sequence Number 1
Notes
Date Text
2001-09-28 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE SERVICE ENTRANCE
 CONDUCTORS? PLEASE NOTE 3-2/0`S AND 1,#1
 PLEASE CALRIFY?
  
 2)NOTE: PLEASE INDICATE200A MAIN PANEL
 AS MCB. SHOWN AS MLO
  
 3)NOTE: PLEASE INCLUDE CWP WITH GROUND-
 -ING ELECTRODE SYSTEM (IF METAL) 250-50
  
 4)NOTE: PLEASE NOTEGARAGE OUTLET TO BE
 SHOWN AS GFI.210-8
  
 5)NOTE:PLEASENOTE THAT ALL BATH OUTLET
 -S ARE ALSO TO BE SHOWN AS GFI/GFI
 PROTECTED PER 210-8
  
 6)NOTE: PLEASE NOTE THAT PANEL SCHEDULES
 SHOW MOETHAN ONE AHU AND CU FOR A/C??
 BUT LOAD CALCULATIONS ONLY SHOW ONE FOR
 HEAT AND PLANS ONLY SHOW ONE CU AND NO
 AHU`S??? PLEASE SHOW ALL AHU`S AND LIGHT
 -S AND RECEPTS IN ATTIC.210-70,210-63
 440-11.
  
 7) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 8)NOTE: PLEASE NOTE CLEARENCES FOR A/C
 CU`S PER 110-26
  
 9)NOTE: PLEASE NOTE THAT LAUNDRY CIRCUIT
 IS SHOWN AT 1200 AND DISHWASHER AT 1500
 THESE COULD BE A MISPRINT AND NEED TO
 BE SWAPPED PER 210-11-C-2
  
 10)NOTE: PLEASE NOTE MISSING OUTLET FOR
 BATH OFF BEDROOM #4, PER 210-52D
  
 11)NOTE: PLEASE NOTE MISSING OUTLET IN
 BEDROOM #4 210-52
  
 12)NOTE: PLEASE NOTE THAT MAIN SHOWN IN
 200A PANEL IS SHOWN AS 180AMPS?? PLEASE
 NOTE THAT THIS NEEDS TO CORRELATE WITH
 ART; 240-6
  
 13)PLEASE NOTE THAT SD FOR MASTER NEEDS
 TO BE MOVED INTO MASTER BEDROOM.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  