| 2001-09-28 00:00:00 | ****************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE NOTE SERVICE ENTRANCE |
| | CONDUCTORS? PLEASE NOTE 3-2/0`S AND 1,#1 |
| | PLEASE CALRIFY? |
| | |
| | 2)NOTE: PLEASE INDICATE200A MAIN PANEL |
| | AS MCB. SHOWN AS MLO |
| | |
| | 3)NOTE: PLEASE INCLUDE CWP WITH GROUND- |
| | -ING ELECTRODE SYSTEM (IF METAL) 250-50 |
| | |
| | 4)NOTE: PLEASE NOTEGARAGE OUTLET TO BE |
| | SHOWN AS GFI.210-8 |
| | |
| | 5)NOTE:PLEASENOTE THAT ALL BATH OUTLET |
| | -S ARE ALSO TO BE SHOWN AS GFI/GFI |
| | PROTECTED PER 210-8 |
| | |
| | 6)NOTE: PLEASE NOTE THAT PANEL SCHEDULES |
| | SHOW MOETHAN ONE AHU AND CU FOR A/C?? |
| | BUT LOAD CALCULATIONS ONLY SHOW ONE FOR |
| | HEAT AND PLANS ONLY SHOW ONE CU AND NO |
| | AHU`S??? PLEASE SHOW ALL AHU`S AND LIGHT |
| | -S AND RECEPTS IN ATTIC.210-70,210-63 |
| | 440-11. |
| | |
| | 7) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | |
| | 8)NOTE: PLEASE NOTE CLEARENCES FOR A/C |
| | CU`S PER 110-26 |
| | |
| | 9)NOTE: PLEASE NOTE THAT LAUNDRY CIRCUIT |
| | IS SHOWN AT 1200 AND DISHWASHER AT 1500 |
| | THESE COULD BE A MISPRINT AND NEED TO |
| | BE SWAPPED PER 210-11-C-2 |
| | |
| | 10)NOTE: PLEASE NOTE MISSING OUTLET FOR |
| | BATH OFF BEDROOM #4, PER 210-52D |
| | |
| | 11)NOTE: PLEASE NOTE MISSING OUTLET IN |
| | BEDROOM #4 210-52 |
| | |
| | 12)NOTE: PLEASE NOTE THAT MAIN SHOWN IN |
| | 200A PANEL IS SHOWN AS 180AMPS?? PLEASE |
| | NOTE THAT THIS NEEDS TO CORRELATE WITH |
| | ART; 240-6 |
| | |
| | 13)PLEASE NOTE THAT SD FOR MASTER NEEDS |
| | TO BE MOVED INTO MASTER BEDROOM. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |