| Plan Review Notes For Permit 01090742 |
| Permit Number |
01090742 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-25 00:00:00 | 1) A NOTICE OF COMMENCEMENT IS REQUIRED | | | PRIOR TO RECEIVING A PERMIT. | | | 2) CLUBHOUSE FIRE PROTECTION SHOWN. | | | CLUBHOUSE FIRE SPRINKLER SYSTEM NOT | | | PART OF THIS PERMIT AND SHOULD BE | | | REMOVED FROM DRAWINGS. | | | 3) ONLY ONE FLOOR AND ROOF FIRE | | | PROTECTION SHOWN. IF THE FLOOR PLAN IS | | | TYPICAL ON THE DRAWINGS FOR ALL FLOORS | | | IT SHOULD BE NOTED AS TYPICAL ON THE | | | DRAWINGS. | | | 4) PLANS ARE MISSING THE FOLLOWING | | | A) POINT OF COMPASS | | | B) CEILING CONSTRUCTION | | | C) FULL HEIGHT CROSS SECTION | | | D) LOCATION OF FIRE WALLS | | | E) LOCATION OF PARTITIONS | | | F) OCCUPANCY OF EACH ROOM OR AREA | | | G) HANGER LOCATIONS | | | H) NUMBER OF SPRINKLERS PER RISER, EACH | | | FLOOR | | | I) LOCATION OF ANY CONCEALED SPACES, | | | ATTICS, CLOSETS. | | | PLEASE PROVIDE AN ENGINEER'S TITLE BLOCK | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|