Plan Review Notes
Plan Review Notes For Permit 01090620
Permit Number 01090620
Review Stop FS
Sequence Number 1
Notes
Date Text
2001-10-10 00:00:001) SOME FIRE SPRINKLER HEADS NOTED ON
 THE PLANS MAY BE INCLUDED IN THE
 VOLUNTARY RECALL BY CENTRAL FIRE
 SPRINKLER COMPANY. PLEASE SEE
 ATTACHED INFORMATION PROVIDED WITH
 PLANS. VERIFICATION IS NEEDED THAT
 FIRE SPRINKLER HEADS PLANNED FOR USE
 ARE NOT PART OF THIS RECALL PLAN.
 PLEASE PROVIDE CUT SHEETS ON FIRE
 SPRINKLER HEADS, PRESSURE REDUCING
 VALVES, PIPE AND OTHER APPURTENANCES
 PLANNED FOR USE.
 2) PLEASE NOTE ON THE PLANS THAT
 PRESSURE TESTS FOR A DURATION OF TWO
 HOURS WILL BE CONDUCTED WITH THE CITY
 FIRE RESCUE DEPARTMENT.
 3) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING AND AFTER CONSTRUCTION.
 4) PLEASE INDICATE WHERE THE SPARE
 HEAD BOX AND WRENCH WILL BE LOCATED.
 5) PLEASE INDICATE ON THE PLANS THAT
 TEMPORARY STANDPIPES WITH FIRE
 DEPARTMENT CONNECTIONS WILL BE PROVIDED
 WHEN THE BUILDING REACHES THREE STORIES
 AND FIFTY FEET IN HEIGHT.
 6) MORE DETAILS NEEDED ON PRESSURE
 REDUCING VALVES.
 7) ALL VALVES ARE TO BE PROPERLY TAGGED.
 PLEASE NOTE THIS ON THE PLANS.
 8) VALUE APPEARS TO BE LOW FOR THE
 SCOPE OF WORK. PLEASE PROVIDE A COPY
 OF THE CONTRACT.
 9) NO HANGERS SHOWN ON THE DRAWINGS.
 10) STANDPIPE SYSTEM TO COMPLY WITH
 NFPA 14. THE STANDPIPE SYSTEM TO BE
 PROVIDE AT LEAST 65 PSI AT THE ROOF
 WHEN FLOWING WATER.
 11) ENTIRE BUILDING IS REQUIRED TO BE
 FIRE SPRINKLER PROTECTED EXCEPT FOR
 RECOGNIZED EXCEPTIONS TO THE CODE.
 ANY SOFFITS INSTALLED ARE NOT TO
 OBSTRUCT FIRE SPRINKLER DISCHARGE
 PATTERNS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved