| Plan Review Notes For Permit 01090539 |
| Permit Number |
01090539 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-09 00:00:00 | *************BUILDING UNSAT************* | | | | | | 1) THE ENERGY FORM INCORRECTLY LISTS THE | | | EXTERIOR WALL TYPE AS WOOD FRAME WITH AN | | | R VALUE OF 3.0. THE EXTERIOR WALLS ARE | | | ACTUALLY CONCRETE BLOCK. PLEASE CORRECT. | | | | | | 2) THE ROOF SHEATHING AT GABLE ENDS IS | | | REQUIRED TO BE NAILED WITH 8D COMMON | | | NAILS AT 4" O.C. AT THE EDGES AND 6"O.C. | | | INTERMEDIATE WITHIN 5' OF THE ROOF EDGE | | | INCLUDING OVERHANG. SEC.2306 CITY OF | | | W.P.B. AMENDMENTS TO THE 97 S.B.C. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|