| Plan Review Notes For Permit 01090531 |
| Permit Number |
01090531 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-09 00:00:00 | THE LEEDCO ENGINEERS ANALYSIS CITES THE | | | 1994 STANDARD BUILDING CODE (SBC) AND A | | | 135 MPH WIND SPEED.THE CITY IS | | | CURRENTLY ENFORCING THE 1997 SBC. | | | ALSO, THIS BUILDING IS A 100' +/- TALL, | | | NOT THE 40' CALLED OUT.THE DESIGN | | | INVESTIGATION SHOULD BE IN ACCORDANCE | | | WITH | | | ASCE 7-95 USING A WIND SPEED BETWEEN | | | THE140 AND 150 MPH CONTOURS FOUND IN | | | FIG. 6-1 OF THAT PUBLICATION. | | | | | | SHEET GN1, 1-1.11 RELATED DOCUMENTS, | | | DOES NOT SHOW THE 1997 SBC AS THE | | | BUILDING CODE DESIGN.THE BOCA CODE | | | CITED ISNOT RECOGNIZED BY THE CITY NOR | | | ARE SPECIFIC EDITIONS OF THE OTHER | | | DESIGN STANDARDS NOTED. | | | | | | | | | SHEET S3, PROVIDE AN ENGINEERING | | | ANALYSIS OR TEST DATA FOR THE VARIOUS | | | ANTENNAE'S ABILITYTO SUSTAIN THE | | | WINDLOADS AT THIS LOCATION. |
|