| Plan Review Notes For Permit 01090497 |
| Permit Number |
01090497 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-20 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO,DURING AND AFTER CONSTRUCTION. | | | 2) VALVES FOR FIRE HYDRANTS SHALL NOT | | | EXCEED 4 FEET FROM THE FIRE HYDRANTS | | | AS SHOWN ON THE DETAIL DRAWINGS. | | | 3) IS THERE ONLY ONE PLANNED INGRESS | | | AND EGRESS ROAD TO THE REAR OF THE | | | PROPERTY. | | | 4) UNDERGOUND FIRE LINES AND | | | FIRE HYDRANTS ARE TO MEET UTILITY AND | | | FIRE RESCUE REQUIREMENTS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|