Date Text
2001-09-18 00:00:00FAILED:
 1. PLEASE PROVIDE STORM WATER CALC..
 2. PLEASE PROVIDE PERVIOUS & IMPERVIOUS
 CALC..
 3. PLEASE PROVIDE R.W GATE VALVE AT
 EVERY 1000' TO 1200' MAX.
 4. R.W GATE VALVE FOR HYDRANT CONNECTION
 SHOULD BE INSTALLED AT 4' MAX. FROM
 C/L OF HYDRANT, SEE STANDARD DETAILS.
 4. PLEASE VERIFY, M.H # 413, 414 ARE
 DROP M.H??
 5. PLEASE SHOW BACKFLOW PREVENTERS FOR
 THE LIFT STATIONS.
 6. PLEASE SHOW ALL DIP SECTIONS @
 CONFLICT CROSSING ON SANITARY SEWER
 PROFILE.
 7. PLEASE PROVIDE POLLUTION PREVENTION
 PLAN, PLAN MUST BE INSTALLED IN FIELD
 PRIOR TO ANY CONSTRUCTION.
 8. PLEASE PROVIDE SIGNING AND MARKING
 PLANS.
 9. NOTE NO. 7 IN GENERAL NOTES, SHEET
 2 OF 7 REFERS TO 1982 SPECS., PLEASE
 REVISE TO LATEST.
 10. INSTALLATION OF LIFT STATIONS AND
 CONNECTIONS TO WATER, SEWER MAIN MUST BE
 COORDINATED AND APPROVED BY PUBLIC
 UTILITIES ENGINEERING SERVICES
 DEPARTMENTS.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI