| 2001-10-04 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - SGC-97 |
| | 1) MORE INFORMATION REQUIRED. IS THIS |
| | KITCHEN FOR COMMERCIAL USE? IS THERE |
| | SEATING? ARE THERE RESTROOM FACILITIES? |
| | 2) PLANS SHALL BE ROUTED TO DEPT. OF |
| | BUSINESS REGULATION FOR REVIEW AND APP- |
| | ROVAL. COUNTYWIDE AMENDMENTS TO SPC-94 |
| | SEC 101.4.7 |
| | 3) WATER FILTRATION SYSTEM SHALL BE NSF |
| | APPROVED PER SPC SEC 615.1 & 615.2. |
| | PLEASE SUBMIT MANUF. INFO. PAGE P0.1 |
| | 4) GREASY WASTE TO DISCHARGE TO GREASE |
| | TRAP. ALL WASTE FROM FLOOR SINKS, FLOOR |
| | DRAINS, 3 COMP SINKS, HAND SINKS ECT. |
| | DISHWASHER SHALL DRAIN TO SANITARY PER |
| | CITY OF WPB ORDINANCE. PAGE P0.1/P2.1 |
| | 5) PAGE P2.1 SCHEDULE OF PLUMBING NOTES |
| | & SYMBOLS. P8 SHOWS 140 DEGREE WATER |
| | FROM HEATER. 11O DEGREE WATER REQUIRED |
| | AT HAND SINK PER FL ENERGY CODE SEC |
| | 412.1 ABCD .2.3.2. TEMPERING VALVE REQ- |
| | UIRED. PLEASE SHOW DETAILS. |
| | 6) PAGE P0.1 PLUMBING NOTES #13 & #18. |
| | AIR CHAMBERS ARE A QUICK FIX. IF NOT RE- |
| | MOVED THEY SHALL COMPLY WITH SPC 607.8.3 |
| | (RECHARGABLE AND ACCESSIBLE) PER WH-PDI |
| | 201. WATER HAMMER ARRESTORS SHALL BE |
| | SIZED AND LOCATED PER MANUFACTURE INSTAL |
| | LATION INSTRUCTIONS AND WH-PDI 201. |
| | PLEASE INDICATE COMPLIANCE ON WATER ISO- |
| | METRIC. |
| | 7) DOMESTIC WATER ISOMETRIC SHOWS SHUT |
| | OFF VALVE FOR WATER HEATER IN CEILING. |
| | VALVE SHALL BE WITHIN 3' OF HEATER PER |
| | SPC SEC 610.3.3. PLEASE SHOW THIS ON |
| | PLAN. PAGE P0.1 |
| | 8) PAGE P2.1 SANITARY PLAN HAS "FD" AT |
| | FLOOR SINKS & "FS" AT FLOOR DRAIN. |
| | PLEASE CORRECT. |
| | 9) GAS (IF USED) SHALL BE ON SEPARATE |
| | PERMIT. (NO GAS SHOWN ON PLAN). |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT. 8377 |