| Plan Review Notes For Permit 01090475 |
| Permit Number |
01090475 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-28 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01090475 | | | 700 S DIXIE HWY | | | CONT: THE WEITZ CO | | | TEL: (561) 686-5511 | | | | | | 1)- THE PLANS DO NOT INDICATE IF THIS IS | | | A ACCESORY OCCUPANCY, A FLOOR PLAN OF | | | THE FIRST FLOOR WILL INDICATE THE USEAGE | | | OR MAIN OCCUPANCY WILL BE. | | | | | | 2)- SBC1203.4.1. THIS SECTION DEALS WITH | | | TOILET ROOMS OPENING DIRECTLY INTO THE | | | ROOM USED FOR PREPARATION OF FOOD, AGAIN | | | THIS PLAN DOESN'T INDICATE WHERE THE FAC | | | ILITIES ARE? | | | | | | 3)- SBC TABLE 803.3 MISSING ARE THE | | | MINIMUM INTERIOR FINISH CLASSIFICATION. | | | | | | 4)- THERE IS A DOOR ON THE LEFT SIDE OF | | | THE PLAN DOES THIS GO TO THE EXTERIOR? | | | IF SO SHOW COMPLIANCE WITH 1205.1.2.3/ | | | 1205.1.2.4. | | | | | | THE PLANS INDICATE THAT A FIRE RATED | | | CHASE WILL EXTEND THROUGH TO THE ROOF, | | | (M2.1) SBC 705.2.3.1 SHOW UL LISTING | | | AND THE TERMINATION DESIGNS. |
|