Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-09-17 00:00:001) OPERATIONAL MATRIX DOES NOT INDICATE
 THAT ALL INITIATING DEVICES WILL SOUND
 THE FIRE ALARM SYSTEM EVACUATION
 FEATURE OF THE FIRE ALARM SYSTEM. PLEASE
 CORRECT OPERATIONAL MATRIX.
 2) OPERATIONAL MATRIX INDICATES THE
 UNLOCKING OF DOORS. WHAT DOORS ARE
 LOCKED.
 3) ELEVATOR EQUIPMENT ROOM M1-47 DOES
 NOT HAVE A HEAT DETECTOR SHOWN.
 4) PLEASE INDICATE ON THE PLANS WHAT
 THE EVACUATION MESSAGE WILL STATE.
 5) PLEASE NOTE ON THE PLANS WHAT
 DEVICES WILL ACTIVATE THE STAIRWELL
 PRESSURIZATION FANS.
 6) PLEASE BE ADVISED THAT SINGLE STATION
 SMOKE DETECTORS ARE REQUIRED IN
 EACH SLEEPING ROOM.
 7) PLEASE INDICATE ON THE PLANS THAT
 SMOKE DETECTORS WILL BE INSTALLED A
 MINIMUM OF THREE FEET FROM HVAC
 DIFFUSERS.
  