| Plan Review Notes For Permit 01090472 |
| Permit Number |
01090472 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-17 00:00:00 | 1) OPERATIONAL MATRIX DOES NOT INDICATE | | | THAT ALL INITIATING DEVICES WILL SOUND | | | THE FIRE ALARM SYSTEM EVACUATION | | | FEATURE OF THE FIRE ALARM SYSTEM. PLEASE | | | CORRECT OPERATIONAL MATRIX. | | | 2) OPERATIONAL MATRIX INDICATES THE | | | UNLOCKING OF DOORS. WHAT DOORS ARE | | | LOCKED. | | | 3) ELEVATOR EQUIPMENT ROOM M1-47 DOES | | | NOT HAVE A HEAT DETECTOR SHOWN. | | | 4) PLEASE INDICATE ON THE PLANS WHAT | | | THE EVACUATION MESSAGE WILL STATE. | | | 5) PLEASE NOTE ON THE PLANS WHAT | | | DEVICES WILL ACTIVATE THE STAIRWELL | | | PRESSURIZATION FANS. | | | 6) PLEASE BE ADVISED THAT SINGLE STATION | | | SMOKE DETECTORS ARE REQUIRED IN | | | EACH SLEEPING ROOM. | | | 7) PLEASE INDICATE ON THE PLANS THAT | | | SMOKE DETECTORS WILL BE INSTALLED A | | | MINIMUM OF THREE FEET FROM HVAC | | | DIFFUSERS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|