| Notes |
| Date |
Text |
| 2001-11-19 00:00:00 | | | | | | | NO MAKE-UP AIR INDICATED ON PLAN FOR | | | THE RESTROOM OR OFFICE AREA.PLEASE | | | SUBMIT REVISED PLAN INDICATING DUCT | | | SIZE, GRILL SIZE AND CFM DISTRIBUTION | | | TO THESE AREAS. | | | | | | PLEASE PROVIDE INFORMATION OF EXISTING | | | RTU (TONNAGE & O.A.).AIR BALANCE | | | SCHEDULE INDICATES 1050 CFM SUPPLY AIR | | | AND PLAN INDICATES 2200 CFM BEING | | | DISTRIBUTED. | | | | | | PROVISO - | | | | | | 1.NO COMBUSTIBLES ABOVE THE CEILING IN | | | THE RETURN AIR PLENUM. | | | 1997 SMC 609.1.1. | | | | | | 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|