| Notes |
| Date |
Text |
| 2001-10-28 00:00:00 | PLUMBING PLAN REVIEW,DENIED | | | (1) SHT-2 PUBLIC REST RM IN STORAGE | | | AREA. | | | STD PLBG. CODE-94, SEC 407.2.2 REQUIRED | | | FACILITIES SHALL BE DIRECTLY ACCESSIBLE | | | TO THE PUBLIC THRU DIRECT OPENINGS OR | | | CORRIDORS FROM THE AREA THEY ARE | | | INTENDED TO SERVE. | | | (2A) SHT-MEP-1 2" PIPE RECEPTOR, ALL | | | INDIRECT WASTE SHALL TERMINATE TO A | | | FLOOR SINK, SEC 802. | | | (2B) PEDICURE UNIT, WATER SUPPLY TO BE | | | PROTECTED WITH A APPROVED BACK FLOW | | | PREVENTER SEC 606. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|