| Plan Review Notes For Permit 01090466 |
| Permit Number |
01090466 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-01 00:00:00 | DENIED; | | | 1.WATER HEATER SHALL BE READILY | | | ACCESSIBLE. INSTALL ON FLOOR OR | | | INSTALL A SHIPS LADDER. | | | 2.T & P LINE TO DRAIN TO A FLOOR SINK | | | WITH A TRAP PRIMER. | | | 3.SHOW COMPLIANCE TO TABLE 407, MINIMUM | | | PLUMBING FIXTURES. | | | 4.WATER DIAGRAM, PLEASE SIZE . | | | 5.WATER HAMMER ARRESTORS SHALL BE | | | INSTALLED PER MANUFACTORS INSTRUCTIONS | | | 6.H/C BATHROOM; | | | A.DOOR NOT PERMITED TO SWING INTO | | | CLEAR FLOOR SPACE OF LAV. FACBC | | | SEC. 4.19.3. | | | B.SHOW GRAB BARS ON FLOOR PLAN. | | | C.REVISE NOTE ABOVE H/C BATH DRAWING | | | HOT WATER LINES AND TRAP WILL BE | | | INSULATED PER 4.19.4 TEMP. NOT IN | | | HANDICAP CODE. | | | 7.SANITARY DIAGRAM NOT CORRECT. LAVITORY | | | NEXT TO PEDICURE SINK IS NOT SHOWN. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|