| Plan Review Notes For Permit 01090448 |
| Permit Number |
01090448 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-21 00:00:00 | PLUMBING PLAN REVIEW. DENIED. | | | (1A) SHT A-1 TOILET RM'S #1,#2 COMPLY | | | WITH FACBC-97 SEC 4.22, LOCATION OF W/C, | | | LAV, GRAB BARS, CLEAR FLR SPACE, DOOR | | | SWING AND TOILET ACCESSORIES. | | | (B) BREAK ROOM SINK COMPLY W/ SEC 4.24 | | | HGTH 34"AFF, KNEE CLEARANCE 19",CLEAR | | | FLOOR SPACE 30"X 48". | | | (C) DRINKING FOUNTAIN REQUIRED, TAB 407 | | | FACBC-97 SEC 4.1.3(10)(A) CLEAR FLOOR | | | SPACE, PEOPLE WHO HAVE TROUBLE BENDING. | | | (D) TOILET ROOMS TO BE DIRECTLY ACCES- | | | SIBLE TO THE PUBLIC, SEC 407.2.2 | | | (2)SHT M-1 PROVIDE A ISOMETRIC DRAWING | | | OF THE DWV AND WATER PIPING, WITH PIPE | | | SIZES, SEC 104.3 | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|