| 2001-10-22 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01090448 | | | 814 N ROSEMARY AV | | | CONT. CATALFUMO | | | TEL 624-9697 X 256 | | | | | | SBC= STANDARD BUILDING CODE 1997 | | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | | | 1)- SBC 3203 DOORS/ WINDOWS SHALL NOT | | | OPEN OR PROJECT UPON PUBLIC PROPERTY. | | | | | | 2)- FL. ACCES. CODE, 4.13.6 MANEUVERING | | | CLEARENCES AT DOORS, SEE DOOR # 3 & 8. | | | 18" IS REQUIRED ON THE PULL SIDE & A | | | MINIMUM OF 12 ON THE PUSH SIDE OF DOOR, | | | AT LATCH. | | | | | | 3)- SHEET A-2 DETAILS 1&2 INDICATE THAT | | | SUSPENDED CEILINGS WILL BE HUNG FROM THE | | | EXISTING PRECAST T'S, HOW ARE THE #9 | | | HANGING WIRE TO BE ATTACHED TO THE | | | PRE-CAST T'S? | | | | | | 4)- SBC 104.1.1 AWNINGS REQUIRE A SSEPER | | | ATE PERMIT. | | | | | | 5)- SBC 3204.2 CLOTH AWNNINGS REQUIRE | | | FIRE RESITANCE CERTIFICATE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096X8412 |
|