Plan Review Notes
Plan Review Notes For Permit 01090435
Permit Number 01090435
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2002-01-10 00:00:001) A REVIEW OF THE FIRE SPRINKLER
 DRAWINGS INDICATE THAT THE NORTH
 BUILDING INCLUDING THE NEW ADDITION
 WILL EXCEED THE 40,000 SQUARE FEET
 PROTECTION AREA LIMITATIONS INDICATED
 IN NFPA 13. ACCORDING TO NFPA 13,
 STORAGE OCCUPANCIES CANNOT EXCEED
 40,000 SQUARE FEET SUPPLIED BY A SINGLE
 RISER A SITE VISIT WAS PERFORMED ON
 1.10.02 BY CITY STAFF. IT IS BELIEVED
 THAT THE EXISTING 1000 GALLON FIRE
 PUMP IS SUPPLIED BY AN EXISTING 6"
 WATER LINE WHICH SHOULD BE AT LEAST
 AN 8" LINE. HIGH-PILED STORAGE WAS
 OBSERVED INSIDE AT LEAST ONE OF THE
 BUILDINGS. IT IS THE OPINION OF CITY
 STAFF THAT A COMPLETE REPORT BE
 PREPARED BY A LICENSED FIRE PROTECTION
 ENGINEER WITH REGARDS TO EXISTING
 FIRE PROTECTION FOR THE BUILDINGS AND
 THE FUTURE FIRE PROTECTION SYSTEM
 PLANNED FOR THE NEW ADDITION. THE
 NEW ADDITION CANNOT BE CONNECTED TO
 THE EXISTING SYSTEM AS IT WOULD EXCEED
 AREA LIMITATIONS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910