| Plan Review Notes For Permit 01090435 |
| Permit Number |
01090435 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-01-10 00:00:00 | 1) A REVIEW OF THE FIRE SPRINKLER | | | DRAWINGS INDICATE THAT THE NORTH | | | BUILDING INCLUDING THE NEW ADDITION | | | WILL EXCEED THE 40,000 SQUARE FEET | | | PROTECTION AREA LIMITATIONS INDICATED | | | IN NFPA 13. ACCORDING TO NFPA 13, | | | STORAGE OCCUPANCIES CANNOT EXCEED | | | 40,000 SQUARE FEET SUPPLIED BY A SINGLE | | | RISER A SITE VISIT WAS PERFORMED ON | | | 1.10.02 BY CITY STAFF. IT IS BELIEVED | | | THAT THE EXISTING 1000 GALLON FIRE | | | PUMP IS SUPPLIED BY AN EXISTING 6" | | | WATER LINE WHICH SHOULD BE AT LEAST | | | AN 8" LINE. HIGH-PILED STORAGE WAS | | | OBSERVED INSIDE AT LEAST ONE OF THE | | | BUILDINGS. IT IS THE OPINION OF CITY | | | STAFF THAT A COMPLETE REPORT BE | | | PREPARED BY A LICENSED FIRE PROTECTION | | | ENGINEER WITH REGARDS TO EXISTING | | | FIRE PROTECTION FOR THE BUILDINGS AND | | | THE FUTURE FIRE PROTECTION SYSTEM | | | PLANNED FOR THE NEW ADDITION. THE | | | NEW ADDITION CANNOT BE CONNECTED TO | | | THE EXISTING SYSTEM AS IT WOULD EXCEED | | | AREA LIMITATIONS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|