Plan Review Notes
Plan Review Notes For Permit 01090435
Permit Number 01090435
Review Stop P
Sequence Number 2
Notes
Date Text
2002-01-04 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT 2, TOILET ROOM TO BE ACCESSIBLE
 AND DESIGNATED UNISEX HDCP TOILET ROOM.
 TABLE 407 REQUIRES 2 W/C'S AND 2 LAVS
 FOR WOMEN.
  
 2) SHT 5, WATER RISER DIAGRAM, AIR CHAM-
 BERS TO BE ACCESSIBLE AND RECHARGEABLE
 PER PDI-WH 201 AND SPC SEC 607.8.3.
 WATER HAMMER ARRESTORS DO NOT REQUIRE
 ACCESS AND SHALL BE LOCATED CLOSE TO
 SOURCE OF SHOCK.
  
 3) SHT 2, DOOR SHALL NOT SWING INTO
 CLEAR FLOOR SPACE OF FIXTURES 4.22.2.
  
 4) SHT 2, PLEASE SHOW DETAILS FOR SINK
 COMPLIANCE SEC 4.24
  
 5) SHT 5, NOTE #12 REMOVE REFERENCE TO
 AIR CHAMBERS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377