| Plan Review Notes For Permit 01090435 |
| Permit Number |
01090435 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-12-14 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE OUTSIDE ARE | | | CALCULATIONS AS PER ASHRAE 62-89. | | | INDICATE CALCULATION ON THE PLAN. | | | | | | PLEASE INDICATE PROTECTION FOR AHU #1, | | | NOTE INDICATES A VERTICAL UNIT BELOW | | | FUTURE STR (STORE?).WILL THIS BE THE | | | SAME OCCUPANT AS THE OFFICE SPACE? | | | | | | PLEASE NOTE AS PER 1997 SMC 609.1.1, NO | | | COMBUSTIBLES SHALL BE ABOVE THE CEILING | | | IN THE RETURN AIR PLENUM. | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR IS | | | REQUIRED AS PER 1997 SMC 406.1. WITH | | | NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS (NFPA 90A | | | 4-4.4.3). | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|