2001-12-14 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE OUTSIDE ARE
 CALCULATIONS AS PER ASHRAE 62-89.
 INDICATE CALCULATION ON THE PLAN.
  
 PLEASE INDICATE PROTECTION FOR AHU #1,
 NOTE INDICATES A VERTICAL UNIT BELOW
 FUTURE STR (STORE?).WILL THIS BE THE
 SAME OCCUPANT AS THE OFFICE SPACE?
  
 PLEASE NOTE AS PER 1997 SMC 609.1.1, NO
 COMBUSTIBLES SHALL BE ABOVE THE CEILING
 IN THE RETURN AIR PLENUM.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR IS
 REQUIRED AS PER 1997 SMC 406.1. WITH
 NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS (NFPA 90A
 4-4.4.3).
  
  