Plan Review Notes
Plan Review Notes For Permit 01090435
Permit Number 01090435
Review Stop E
Sequence Number 2
Notes
Date Text
2001-12-11 00:00:00*************** UNSAT **************
  
 PLEASE NOTE THAT NOTE#1&2 FROM FIRST
 REVIEW IS NOT SHOWN ON PLANS.
 PLEASE NOTE THAT LOAD CALCUALTIONS,
 NEED TO BE SHOWN AS ON FIRST SET OF
 NOTES. PLEASE SEE 215-5,220-3, 220-3-B9,
 215-2,215-3,230-42,,,,PLEASE CLARIFY
 WHERE 125% IS SHOWN?
 PLEASE NOTE IF METHOD OF EQUIPMENT
 GRONDING IS A METAL CONDUIT THEN PLEASE
 SHOW ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372