| 2001-10-27 00:00:00 | PLUMBING PLAN REVIEW,DENIED |
| | CODE REFERENCE, SPC-94, FACBC-97 |
| | (1) TAB 407 MINIMUM FACILITIES, WOMEN'S |
| | REST RM, REQUIRED 2-W/C, 2-LAV'S. |
| | (2) SHT-2,FACBC SEC 4.1 MIN. REQUIRMENTS |
| | ALL AREAS OF NEWELY DESIGNED OR CONSTRU- |
| | CTED BUILDINGSAND FACILITIES REQUIRED |
| | TO BE ACCESSIBLE, SHALL COMPLY WITH 4.16 |
| | ALTERATIONS TO EXISTING BUILDINGS. |
| | PROVIDE DETAILS OF H/C FIXTURES,SEE FIGS |
| | PAGES 102 THRU 109 FACBC-97. |
| | SHOW CLEAR FLOOR SPACE FOR EA FIXTURE. |
| | DOORS SHALL NOT SWING INTO CLEAR FLOOR |
| | SPACE REQUIRED FOR ANY FIXTURE 4.22.2 |
| | BREAK RM SINK, SEC 4.24 SINKS. |
| | (3) SHT-5,DWV ISOMETRIC, D/F, URINAL |
| | NOT VENTED. |
| | (4A) SHT-5, PROVIDE ISOMETRIC FOR WATER |
| | PIPING,PIPE SIZES,SHOW LOCATION OF WATER |
| | HEATER,BACK FLOW PREVENTER. |
| | (B) NOTE #12 REFERENCE TO AIR CHAMBERS, |
| | SEC 607.8.3 ACCESSIBLE, RECHARGEABLE. |
| | SPECIFY TYPE AND LOCATION OF WATER SHOCK |
| | ARRESTOR.PDI-WH201, ASSE 1010. |
| | END OF COMMENTSPAUL SCHMITZ |