| Plan Review Notes For Permit 01090435 |
| Permit Number |
01090435 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-24 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT LOAD CALCALAT- | | | -IONS NEED TO BE SHOWN!!215-5 | | | ALL CONTINOUS LOADS AT 125% | | | PLEASE NOTE PLANS SHOW CONNECTED LOADS | | | W/NO WATTS PER SQ FT, OUTLETS ETC | | | | | | 2)NOTE: PLEASE CLARIFY EQUIPMENT | | | GROUNDING BETWEEN FIRST MEANS OF DISC | | | AND PANELS?? 250-122 | | | | | | | | | 3)NOTE: PLEASE NOTE THAT ALL PLANS MUST | | | CONTAIN AN ORIGINAL SIGNATURE FROM THE | | | ARCH/ENGINEER OF RECORD PER FS/FAC | | | 471.025/481.221 | | | PLEASE NOTE THAT PLANSHAVE A STAMP FOR | | | SIGNATURE? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|