Plan Review Notes
Plan Review Notes For Permit 01090435
Permit Number 01090435
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-24 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT LOAD CALCALAT-
 -IONS NEED TO BE SHOWN!!215-5
 ALL CONTINOUS LOADS AT 125%
 PLEASE NOTE PLANS SHOW CONNECTED LOADS
 W/NO WATTS PER SQ FT, OUTLETS ETC
  
 2)NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING BETWEEN FIRST MEANS OF DISC
 AND PANELS?? 250-122
  
  
 3)NOTE: PLEASE NOTE THAT ALL PLANS MUST
 CONTAIN AN ORIGINAL SIGNATURE FROM THE
 ARCH/ENGINEER OF RECORD PER FS/FAC
 471.025/481.221
 PLEASE NOTE THAT PLANSHAVE A STAMP FOR
 SIGNATURE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372