| 2001-10-26 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01090435 |
| | 1600 N. FLORID MANGO DOAD |
| | CONT: MCKINNEY COMMERCIAL CONST.GR. |
| | TEL: (321) 727-0059 |
| | |
| | SBC= 1997 STANDAED BUILDING CODE |
| | SBC*= AMENDMENTS/ STANDARD BUILDING CODE |
| | |
| | 1)- SBC* 104.2.2 ADDITIONAL INFORMATION |
| | REQUIRED, A CURRENT SURVEY. SBC 503.4.1 |
| | /60' CLEAR AREA FOR AREA MODIFICATIONS. |
| | |
| | 2)- SBC* PLANS DO NOT INDICATE TYPE OF |
| | BUILDING TYPE I- VI. IS THE CURRENT |
| | BUILDINGS FULLY SPRINKLERED? WILL THE |
| | ADDITION AS WELL AS THE OFFICE BE FULLY |
| | SPRINKLERED? |
| | |
| | 3)- 8 1/2"X11" DETAIL SHEET, ALTERNATE |
| | SECTIION, THIS DETAIL INDICATES 16" |
| | FLOOR TRUSSES,AGAIN WHAT TYPE CONSTRUC- |
| | TION ARE YOU USING? WHAT TYPE OCCUPANCY |
| | WILL THE AREA ABOVE THE 16" FLOOR TRUSS- |
| | ES BE USED FOR? STORAGE, ADMINISTTRATIVE |
| | CODE 106.4.2 STORAGE & FACTORY OWNER, |
| | AGENT SHALL EMPLOY A COMPETENT ARCHITECT |
| | OR ENGINEER IN COMPUTING THE SAFE FLOOR |
| | LOAD CAPACITY. ALL SUCH COMPUTATIONS |
| | SHALL BE ACCOMPANIED BY AN AFFIDAVIT |
| | FROM THE DESIGN PROFESSIONAL STATING THE |
| | SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR |
| | IN POUNDS PER SQUARE FOOTUNIFORMLY |
| | DISTRIBUTED.THE COMPUTATIONS & AFFIDAVIT |
| | SHALL BE FILED AS A PERMANENT RECORD OF |
| | THE BUILDING DEPARTMENT. |
| | |
| | 4)- SBC 411.1.1 HIGH RACK STORAGE, |
| | PLEASE PROVIDE INFORMATION ON STORAGE |
| | COMPONENTS? |
| | |
| | 5)- NEW ADDITION, WILL PRODUCT APPROVAL |
| | FOR THE SWING DOORS, OVERHEAD DOORS AS |
| | WELL AS THEROOFING BE SUBMITTED WITH |
| | SHOP DRAWINGS? |
| | |
| | 6)- THE DESIGN PROFESSIONALS ARE TO |
| | ADDRESS THE DESIGN DIFFERERENCIAL OF THE |
| | OLD STRUCTURE, THE ABILITY OF THE EXIST |
| | ING STRUCTURE (DESIGNED UNDER PREVIOUS |
| | CODES) TO WITHSTAND THE WIND LOADS AND |
| | DESIGN PRESSURES OF TODAYS CODE? |
| | |
| | 7)- OFFICE SPACE: FL.ACC CODE 4.1.6(2) |
| | PLEASE INDICATE THE HANDICAPPED EGRESS |
| | INTO THE OFFICES. |
| | |
| | 8)- MENS RESTROOM :FL ACC CODE 4.17.5 |
| | DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE OF ANY FIXTURE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 EX 8412 |