| 2001-09-19 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01090332 |
| | 1601 BELVEDERE RD./ #211 |
| | SERVICO CENTRE ASSOCIATES, LTD. |
| | TEL: (561) 394-5200 |
| | FAX: (561) 394-5498 |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | "PLAN REVIEW" |
| | 1)- SHEET #1 INDICATES THAT WOOD BUCKS |
| | WILL BE USED, SBC 604/ 609.2.1 TYPE I& |
| | TYPE II BUILDINGS REQUIRE NON-COMBUST- |
| | IBLE MATERIALS IN WALLS, BACKING, BUCKS |
| | ARE INCLUDED, FIRE RESISTANT TREATED |
| | WOOD IS ACCEPTED. |
| | |
| | 2)- SHEET #3 GENERAL NOTES, NOTE #1, |
| | THIS BUILDING IS A TYPE I /OR TYPE II |
| | BUILDING APPROX. 16 STORIES HIGH. |
| | |
| | 3)- SBC 1004.1.4. ARRANGEMENTS & NUMBER |
| | OF EXITS. WHERE 2 OR MORE EXITS OR EXIT |
| | ACCESS DOORS ARE REQUIRED, AT LEAST 2 OF |
| | THE EXIT DOORS SHALL BE PLACED A DIS- |
| | TAANCE APART EQUAL TO NOT LESS THAN ONE |
| | HALF THE LENGTH OF THE MAXIMUM DIAGONAL |
| | DIMENSION OF THE BUILDING OR AREA. |
| | |
| | 4)_SBC TABLE 803.3 MISSING INFORMATION |
| | FOR MINIMUM INTERIOR FINISH CLASSIFICA- |
| | TION. |
| | |
| | 5)- TYPE I TYPE II BUILDINGS ARE |
| | REQUIRED TO HAVE FIRE SPRINKLERS, PLANS |
| | FOR FIRE SPRINKLERS THERE LAYOUT ALL |
| | DEVICESTO BE INCLUDED BEFORE A BUILD- |
| | ING PERMIT CAN BE ISSUED. |
| | |
| | 6)- FL ACCESSIBILITY CODE4.1.6.2.2. |
| | ALTERATIONA MADE TO PROVIDE AN ACCESS- |
| | IBLE PATH OF TRAVEL TO ALTERED AREAS |
| | SHALL BE DEEEMED DISPROPORTIONATE TO THE |
| | OVERALL ALTERATION WHEN THE COST EXCEEDS |
| | 20 % OF THE CODT OF THE ALTERATION TO |
| | THE PRIMARY FUNCTION AREA. |
| | |
| | THE CONTRACTOR TO SHOW WHERE $4,000 WILL |
| | BE USED UP DATING THE AREA TO THE FL |
| | ACCESSIBILITY CODE, SHEET 3 NOTE 21 WILL |
| | QUALIFY AS PART OF THESE MONIES REQUIRED |
| | TO BE ALLOCATED. |
| | THE CONFRENCE ROOM DOOR DOESN'T MEET THE |
| | MANEUVERING CLEARENCES 4.13.6. |
| | |
| | BUILDING PLAN REVIEW |