Plan Review Notes
Plan Review Notes For Permit 01090320
Permit Number 01090320
Review Stop M
Sequence Number 1
Notes
Date Text
2001-09-13 00:00:00******************PROVISO***************
  
 AHU IN ATTIC SHALL COMPLY WITH 1997 SMC
 304.1.1,ACCESS OPENING SHALL BE NO
 LESS THAN 22" X 36" CONTINUOUS FROM THE
 OPENING TO THE EQUIPMENT AND ITS
 CONTROLS.
  
 EQUIPMENT IN THE ATTIC SHALL HAVE AN
 ACCESSIBLE DISCONNECT SWITCH AND A
 110-120 VOLT A/C GROUNDING TYPE
 CONVENIENCE OUTLET.A LIGHT ON THE
 SERVICE SIDE OF THE EQUIPMENT CONTROLED
 BY A SWITCH AT THE ACCESS OPENING.
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED FOR AHU AS PER 1997
 SMC 304.8.6.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved