| Plan Review Notes For Permit 01090320 |
| Permit Number |
01090320 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-13 00:00:00 | ******************PROVISO*************** | | | | | | AHU IN ATTIC SHALL COMPLY WITH 1997 SMC | | | 304.1.1,ACCESS OPENING SHALL BE NO | | | LESS THAN 22" X 36" CONTINUOUS FROM THE | | | OPENING TO THE EQUIPMENT AND ITS | | | CONTROLS. | | | | | | EQUIPMENT IN THE ATTIC SHALL HAVE AN | | | ACCESSIBLE DISCONNECT SWITCH AND A | | | 110-120 VOLT A/C GROUNDING TYPE | | | CONVENIENCE OUTLET.A LIGHT ON THE | | | SERVICE SIDE OF THE EQUIPMENT CONTROLED | | | BY A SWITCH AT THE ACCESS OPENING. | | | | | | AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED FOR AHU AS PER 1997 | | | SMC 304.8.6.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|