| Notes |
| Date |
Text |
| 2001-09-25 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW: | | | | | | 1.EXHAUST FAN 2 IS NOT INDICATED ON | | | PLAN. | | | | | | 2.PROVIDE AIR BALANCE SCHEDULE TO | | | SHOW COMPLAINCE WITH 1997 SMC 501.2. | | | | | | 3.AHU SHALL HAVE SUFFICIENT CLEARANCE | | | FOR ACCESSIBILITY FOR SERVICE AND | | | REPLACEMENT OF FILTERS, BLOWERS, | | | MOTORS, COILS, CONTROLS AND VENT | | | CONNECTIONS. | | | | | | 4.PLEASE EXPLAIN THE 4" X 8" GRILL | | | IS IT PULLING MAKE-UP AIR FROM | | | THE INTERIOR SPACE? | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|