Plan Review Notes
Plan Review Notes For Permit 01090308
Permit Number 01090308
Review Stop M
Sequence Number 1
Notes
Date Text
2001-09-25 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.EXHAUST FAN 2 IS NOT INDICATED ON
 PLAN.
  
 2.PROVIDE AIR BALANCE SCHEDULE TO
 SHOW COMPLAINCE WITH 1997 SMC 501.2.
  
 3.AHU SHALL HAVE SUFFICIENT CLEARANCE
 FOR ACCESSIBILITY FOR SERVICE AND
 REPLACEMENT OF FILTERS, BLOWERS,
 MOTORS, COILS, CONTROLS AND VENT
 CONNECTIONS.
  
 4.PLEASE EXPLAIN THE 4" X 8" GRILL
 IS IT PULLING MAKE-UP AIR FROM
 THE INTERIOR SPACE?
  