| Plan Review Notes For Permit 01090294 |
| Permit Number |
01090294 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-02 00:00:00 | DENIED | | | REFERENCE: SPC-94 - SGC-97 - FACBC-97 | | | | | | 1) PAGE A5, SANITARY RISER VENT REQUIRED | | | BEFORE 1ST WAIT STATION. (SHOWN ON FLAT | | | DRAWING) SPC SEC 921.4.2 | | | 2) PAGE A5, COMBINATION WASTE AND VENT | | | FOR FLOOR SINKS AND HAND SINK AT BAR | | | AREA TO COMPLY WITH SEC 421.4. PIPE SIZE | | | TO BE AT LEAST 4" FOR MAIN HORIZONTAL | | | WASTE LINE. | | | 3) PAGE A5, WATER RISER, MAXIMUM FIX- | | | TURES ON 1/2" COLD WATER IS 2. SPC-94 | | | COUNTYWIDE AMENDMENTS SEC 607.7 | | | 4) PAGE A5, FLOOR DRAINS IN PUBLIC REST | | | ROOMS SHALL HAVE TRAP PRIMERS. SPC 94 | | | SEC 409.4.1.1 | | | 5) PAGE A5, UNIT #19 4 WELL STEAM TABLE | | | SHALL DRAIN INTO A FLOOR SINK NOT A | | | FLOOR DRAIN AS SHOWN ON GREASE RISER & | | | FLAT DRAWING. SPC-94 SEC 804.1 804.5 | | | 6) PAGE A1, SHOW DETAIL ON HDCP URNAL. | | | CLEAR FLOOR SPACE & HEIGHT PER FACBC-97 | | | SEC 4.18.2 & 4.18.3 | | | 7) PAGES C1 & A5, GREASE TRAP TO BE | | | SIZED BY UTILITY DEPT.PLEASE CONTACT | | | R. COMPO AT (561) 837-4074. | | | 8) PAGE A5, SEPARATE PERMIT REQUIRED FOR | | | GAS. SEE ATTACHED SHEET FOR INFORMATION | | | REQUIRED WITH PERMIT APPLICATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|