Plan Review Notes
Plan Review Notes For Permit 01090294
Permit Number 01090294
Review Stop P
Sequence Number 1
Notes
Date Text
2001-10-02 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) PAGE A5, SANITARY RISER VENT REQUIRED
 BEFORE 1ST WAIT STATION. (SHOWN ON FLAT
 DRAWING) SPC SEC 921.4.2
 2) PAGE A5, COMBINATION WASTE AND VENT
 FOR FLOOR SINKS AND HAND SINK AT BAR
 AREA TO COMPLY WITH SEC 421.4. PIPE SIZE
 TO BE AT LEAST 4" FOR MAIN HORIZONTAL
 WASTE LINE.
 3) PAGE A5, WATER RISER, MAXIMUM FIX-
 TURES ON 1/2" COLD WATER IS 2. SPC-94
 COUNTYWIDE AMENDMENTS SEC 607.7
 4) PAGE A5, FLOOR DRAINS IN PUBLIC REST
 ROOMS SHALL HAVE TRAP PRIMERS. SPC 94
 SEC 409.4.1.1
 5) PAGE A5, UNIT #19 4 WELL STEAM TABLE
 SHALL DRAIN INTO A FLOOR SINK NOT A
 FLOOR DRAIN AS SHOWN ON GREASE RISER &
 FLAT DRAWING. SPC-94 SEC 804.1 804.5
 6) PAGE A1, SHOW DETAIL ON HDCP URNAL.
 CLEAR FLOOR SPACE & HEIGHT PER FACBC-97
 SEC 4.18.2 & 4.18.3
 7) PAGES C1 & A5, GREASE TRAP TO BE
 SIZED BY UTILITY DEPT.PLEASE CONTACT
 R. COMPO AT (561) 837-4074.
 8) PAGE A5, SEPARATE PERMIT REQUIRED FOR
 GAS. SEE ATTACHED SHEET FOR INFORMATION
 REQUIRED WITH PERMIT APPLICATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377