2001-09-24 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090294
 1649 FORUM PLACE
 CONT: BUILDING ASSOCIATES INC
 TEL: (561) 746-3421
 CEL: (561) 310-5429
  
 SBC = STANDARD BUILDING CODE
  
 1)- SHEET A1 INDICATES EXTERIOR DOORS
 # 4,5 & 8. THERE IS NO PLOT PLAN, THE
 KEY PLAN DOESN'T INDICATE WHERE THE PROP
 ERTY LINE IS IN RELATIONSHIP WITH THESE
 OPENINGS. SBC 705 1.1.2. PROTECTION OF
 EXTERIOR WALL OPENINGS, EVERY EXTERIOR
 WALL OPENING WITHIN 15' OF THE PROPERTY
 LINE SHALL BE EQUIPPED WITH APPROVED
 OPENING PROTECTIVES.
  
 2)- SHEET A1 INDICATES THAT THERE WAS A
 DOORWAY BLOCKED IN AT APPROXIMATELY
 DOOR #5, IS DOORWAY #5 A NEW OPENING RE-
 QUIRING THE LINTEL? IF SO DO THE BLOCK
 CELLS ON EITHER SIDE OF THE DOORWAY
 REQUIRE REINFORCING?
  
 3)- SHEET A1 ALSO INDICATES THAT DOOR
 #4 IS TO BE REPLACED, WILL THE DOOR JAMB
 ALSO BE REPLACED?
  
 4)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 EXTERIOR DOOR ASSEMBLIES (DOOR & JAMBS)
 THAT ARE REPLACED SHALL COMPLY WITH
 WIND ZONE TESTING REQUIREMENT TESTING.
 110 MPH WIND ZONE. THE CITY ACCEPTS
 DADE COUNTY OR SBCCI TEST REPORTS,
 (2 COPIES).
  
 5)- SBC 1205 RODENT PROOFING, EXTERIOR
 WALL OPENINGS TO COMPLY WITH THIS SEC-
 TION OF THE CODE.
  
 6)- SHEET A1 INDICATES THAT THERE WILL
 BE NEW GLAZING (WINDOW) THE CITY SHALL
 REQUIRE PRODUCT TESTING REPORTS,THE TEST
 ING REPORT WILL NEED ONLY SHOW TESTING
 FOR WIND, SINCE LESS THAN 50% OF THE
 GLAZED OPENINGS ARE NOT BEING REPLACED
 THIS STRUCTURE DOES NOT REQUIRE NEED TO
 MEET THE REQUIREMENTS FOR LARGE MISSLE
 IMPACT GLAZING. SBC 1606.4/1707/4/1.
 CITY OFFICIAL INTERPRETATION (4).
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412