Plan Review Notes
Plan Review Notes For Permit 01090276
Permit Number 01090276
Review Stop M
Sequence Number 2
Notes
Date Text
2001-12-12 00:00:00********************DENIED**************
  
  
 1.DUCT SYSTEM SHALL BE DESIGNED AND
 INSTALLED IN A MANNER TO PROVIDE AN
 AIR VELOCITY WITHIN THE DUCT SYSTEM
 OF NOT LESS THAN 1,500 FT PER
 MINUTE.
  
 PLAN SHEET 1 OF 2 INDICATES 1,489
 FPM.
  
 AS PER 1997 SMC 505.5.4, DUCTWORK
 CONNECTED TO BOTH SIDES OF THE FAN SHALL
 HAVE ACCESS FOR INSPECTION AND CLEANING
 WITHIN 3 FT ON EACH SIDE OF THE FAN.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.