| 2001-12-12 00:00:00 | ********************DENIED************** | | | | | | | | | 1.DUCT SYSTEM SHALL BE DESIGNED AND | | | INSTALLED IN A MANNER TO PROVIDE AN | | | AIR VELOCITY WITHIN THE DUCT SYSTEM | | | OF NOT LESS THAN 1,500 FT PER | | | MINUTE. | | | | | | PLAN SHEET 1 OF 2 INDICATES 1,489 | | | FPM. | | | | | | AS PER 1997 SMC 505.5.4, DUCTWORK | | | CONNECTED TO BOTH SIDES OF THE FAN SHALL | | | HAVE ACCESS FOR INSPECTION AND CLEANING | | | WITHIN 3 FT ON EACH SIDE OF THE FAN. | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|