2002-03-11 00:00:00FLOOR TRUSSES DENIED
  
 1) PLEASE SUBMIT (2) TWO SETS OF TRUSS
 DRAWINGS AND LAYOUTS. (REQUIRED)
  
 2) THE TRUSS DRAWINGS AND LAYOUT REQUIRE
 THE ORIGINAL WET SIGNATURE, DATE AND
 EMBOSSED SEAL OF THE TRUSS ENGINEER.
  
 3) THE DRAWINGS AND LAYOUT ARE REQUIRED
 TO BE REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD FOR THE STRUCTURE.
 THE LAYOUT MUST BE STAMPED REVIEWED AND
 APPROVED BY THE ARCHITECT OR ENGINEER
 AND BE SIGNED BY THEM.
  
 4) SPECIFY ON THE TRUSS DRAWINGS AND
 LAYOUT THE DESIGN CRITERIA THAT IS BEING
 USED TO DESIGN THE TRUSSES.THE STRUCTURE
 WAS DESIGNED USING THE 1997 STANDARD
 BUILDING CODE SECTION 1606 WITH 110 MPH
 WIND SPEED (FASTEST MILE).
  
 5) THE ROOF TRUSS INFORMATION SUBMITTED
 (VALLEY DETAIL, PIGGYBACK, ETC.) IS NOT
 REQUIRED FOR FLOOR TRUSS REVIEW.
  