| Plan Review Notes For Permit 01090226 |
| Permit Number |
01090226 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-10-31 00:00:00 | *************BUILDING UNSAT************* | | | | | | 1) PERMIT CAN NOT BE ISSUED UNTIL PLANS | | | APPROVED BY THE HISTORIC PRESERVATION | | | BOARD WITH THE PARAPET WALL (GUARDRAIL) | | | AROUND THE BALCONY ARE SUBMITTED FOR | | | REVIEW. STRUCTURAL DRAWINGS MUST BE | | | SIGNED, SEALED AND DATED BY THE DESIGNER | | | OF RECORD (ENGINEER). | | | | | | 2) INDICATE NUMBER, SIZE AND LOCATION OF | | | SCUPPERS AND OVERFLOW SCUPPERS ON THE | | | PLANS. SCUPPERS AND OVERFLOWS MUST | | | COMPLY WITH CHAPTER 11 OF THE S.P.C. AND | | | SECTION 1517.6.4 OF THE SBC. | | | | | | 3) THE DRAWN IN OR RED LINED REVISIONS | | | TO THE PLANS MUST BE INITIALED BY THE | | | DESIGNER OF RECORD (ENGINEER). | | | | | | 4) PROVIDE ENERGY CALCULATIONS | | | AS REQUIRED BY THE 1997 FLORIDA ENERGY | | | EFFICIENCY CODE FOR BUILDING | | | CONSTRUCTION. (THEY WERE MISSING FROM | | | RESUB) | | | | | | 5) PROVIDE PRODUCT APPROVALS FOR DOUBLE | | | HUNG WINDOWS. | | | | | | 6) SEPARATE PERMITS AND WILL BE REQUIRED | | | FOR ROOFING, MECHANICAL AND ELECTRICAL. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|