| Plan Review Notes For Permit 01090226 |
| Permit Number |
01090226 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-02 00:00:00 | *******************DENIED*************** | | | | | | | | | 1.PLEASE PROVIDE INFORMATION ON THE | | | EXISTING A/C. | | | | | | A.MAKE, MODEL, BTU & SEER/EER | | | RATING. | | | | | | B.WHAT IS THE SQUARE FOOTAGE THAT | | | THE UNIT IS CURRENTLY SUPPLYING | | | AIR TO.NO CALCS ARE SUPPLIED | | | TO DETERMINE IF EXISTING UNIT | | | WILL BE ABLE TO SUPPLY AN | | | ADDITIONAL 410 CFM AS INDICATED | | | ON THE PLAN TO THE MASTER BED | | | ROOM. | | | | | | 3.ENERGY CALCS NEED TO ACCOMPANIED BY | | | THE ACCA MANUAL J, ACCA MANUAL N, OR | | | THE ASHRAE COOLING AND HEATING LOAD | | | CALCULATION MANUAL AS PER FLORIDA | | | ENERGY CODE SECTION 607.1.ABC.1. | | | | | | 4.INICATE ON THE PLAN WHERE THE | | | EXISTING AIR HANDLER UNITS RETURN | | | AIR IS LOCATED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|