2001-10-02 00:00:00*******************DENIED***************
  
  
 1.PLEASE PROVIDE INFORMATION ON THE
 EXISTING A/C.
  
 A.MAKE, MODEL, BTU & SEER/EER
 RATING.
  
 B.WHAT IS THE SQUARE FOOTAGE THAT
 THE UNIT IS CURRENTLY SUPPLYING
 AIR TO.NO CALCS ARE SUPPLIED
 TO DETERMINE IF EXISTING UNIT
 WILL BE ABLE TO SUPPLY AN
 ADDITIONAL 410 CFM AS INDICATED
 ON THE PLAN TO THE MASTER BED
 ROOM.
  
 3.ENERGY CALCS NEED TO ACCOMPANIED BY
 THE ACCA MANUAL J, ACCA MANUAL N, OR
 THE ASHRAE COOLING AND HEATING LOAD
 CALCULATION MANUAL AS PER FLORIDA
 ENERGY CODE SECTION 607.1.ABC.1.
  
 4.INICATE ON THE PLAN WHERE THE
 EXISTING AIR HANDLER UNITS RETURN
 AIR IS LOCATED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.