Plan Review Notes
Plan Review Notes For Permit 01090226
Permit Number 01090226
Review Stop E
Sequence Number 1
Notes
Date Text
2001-10-01 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3)NOTE: PLEASE NOTE THATNEW FOOTER
 STEEL TO BE BONDED TO SERVICE. 250-50
  
 4)NOTE: PLEASE CLARIFY RISER DIAGRAM
 SHOWING MAIN DISCONNECT, BUT PLANS DO
 NOT SHOW MAIN NEXT TO METER. PLEASE ALSO
 CLARIFY THE MAIN PANEL BEING SHOWN WITH
 A MCB.?
  
 5) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372