| 2001-11-02 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 |
| | |
| | 1) PREVIOUS COMMENT NOT ADDRESSED. |
| | PAGE A4.0, BAR ELEVATION (8) PLEASE |
| | COMPLY WITH FACBC SEC 4.24. PROVIDE |
| | DETAILS ON PLANS. |
| | 2) PREVIOUS COMMENT NOT ADDRESSED. |
| | PAGE A4.0 MENS RESTROOM (6)(11) URNALS |
| | PLEASE COMPLY WITH FABC SEC 4.18 AND |
| | 4.22.5 |
| | 3) PREVIOUS COMMENT NOT ADDRESSED. PAGE |
| | P1.0 WATER HEATER TO BE READILY ACCESS- |
| | ABLE PER SPC SEC 501.7. PLEASE PROVIDE A |
| | PERMINATE SHIPS LADDER AND A WORKING |
| | PLATFORM FOR SERVICING, MINIMUM 30"X30" |
| | 4) PREVIOUS COMMENT NOT ADDRESSED. PAGE |
| | P2.0 SANITARY ISOMETRIC. MENS ROOM URNAL |
| | AND ELECT. WATER COOLER CAN NOT DRAIN TO |
| | STACK ON A CROSS FITTING. PLEASE HAVE |
| | FIXTURES DRAIN TO STACK AT DIFFERENT |
| | HEIGHTS. |
| | 5) PREVIOUS COMMENT NOT ADDRESSED. PAGE |
| | P2.0 WATER ISOMETRIC/PAGE P3.0 GENERAL |
| | NOTES #16 AIR CHAMBERS ARE QUICK FIX AND |
| | WATER HAMMER ARRESTORS SHOULD BE USED. |
| | HAMMER ARRESTORS SHALL PLACED PER MANU- |
| | FACTURE INSTALLATION INSTRUCTIONS AND |
| | WH-PDI 201 NOT AT TOP OF DROP AS SHOWN |
| | AT LAV IN MENS ROOM. ALSO SHOW SHUT OFF |
| | VALVES AT ALL HOSE BIBBS. |
| | 6) PREVIOUS COMMENT NOT ADDRESSED. PAGE |
| | A4.0 & P1.0 DRINKING FOUNTAIN PLEASE |
| | COMPLY WITH FACBC SEC 5.15 & SEC 4.1.3 |
| | (10)(A) FOR THOSE WHO HAVE DIFFICULTY |
| | BENDING OR STOOPING. |
| | 7) PREVIOUS COMMENT NOT ADDRESSED. |
| | PLEASE PROVIDE CALCULATIONS FOR MINIMUM |
| | FACILITIES FOR FIXTURES. USE SCP TABLE |
| | 407. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |