2001-11-02 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PREVIOUS COMMENT NOT ADDRESSED.
 PAGE A4.0, BAR ELEVATION (8) PLEASE
 COMPLY WITH FACBC SEC 4.24. PROVIDE
 DETAILS ON PLANS.
 2) PREVIOUS COMMENT NOT ADDRESSED.
 PAGE A4.0 MENS RESTROOM (6)(11) URNALS
 PLEASE COMPLY WITH FABC SEC 4.18 AND
 4.22.5
 3) PREVIOUS COMMENT NOT ADDRESSED. PAGE
 P1.0 WATER HEATER TO BE READILY ACCESS-
 ABLE PER SPC SEC 501.7. PLEASE PROVIDE A
 PERMINATE SHIPS LADDER AND A WORKING
 PLATFORM FOR SERVICING, MINIMUM 30"X30"
 4) PREVIOUS COMMENT NOT ADDRESSED. PAGE
 P2.0 SANITARY ISOMETRIC. MENS ROOM URNAL
 AND ELECT. WATER COOLER CAN NOT DRAIN TO
 STACK ON A CROSS FITTING. PLEASE HAVE
 FIXTURES DRAIN TO STACK AT DIFFERENT
 HEIGHTS.
 5) PREVIOUS COMMENT NOT ADDRESSED. PAGE
 P2.0 WATER ISOMETRIC/PAGE P3.0 GENERAL
 NOTES #16 AIR CHAMBERS ARE QUICK FIX AND
 WATER HAMMER ARRESTORS SHOULD BE USED.
 HAMMER ARRESTORS SHALL PLACED PER MANU-
 FACTURE INSTALLATION INSTRUCTIONS AND
 WH-PDI 201 NOT AT TOP OF DROP AS SHOWN
 AT LAV IN MENS ROOM. ALSO SHOW SHUT OFF
 VALVES AT ALL HOSE BIBBS.
 6) PREVIOUS COMMENT NOT ADDRESSED. PAGE
 A4.0 & P1.0 DRINKING FOUNTAIN PLEASE
 COMPLY WITH FACBC SEC 5.15 & SEC 4.1.3
 (10)(A) FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
 7) PREVIOUS COMMENT NOT ADDRESSED.
 PLEASE PROVIDE CALCULATIONS FOR MINIMUM
 FACILITIES FOR FIXTURES. USE SCP TABLE
 407.
  