| 2001-10-25 00:00:00 | *******************DENIED*************** | | | | | | PLANS ARE NOT SEALED BY ENGINEER OF | | | RECORD. | | | | | | FIRE DEPT COMMENTS FOR MECHANICAL | | | CLOSET HAVING A 1 HOUR FIRE RATING. | | | FIRE DAMPERS WILL BE REQUIRED AT THESE | | | PENETRATIONS.PLEASE INDICATE FIRE | | | DAMPERS ON PLAN AND SHOW DETAIL FOR | | | INSTALLATIONAS PER 1997 SMC 610.1.2. | | | FIRE DAMPERS SHALL COMPLY WITH THE | | | REQUIREMENTS OF UL 555. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|