Plan Review Notes
Plan Review Notes For Permit 01090187
Permit Number 01090187
Review Stop P
Sequence Number 1
Notes
Date Text
2001-10-03 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
 1) PLEASE NOTE THAT ALL PLANS SUBMITTED
 BY AN ENGINEER ARE TO BE SIGNED, DATED,
 AND SEALED BY PERSON OF RECORD. PLEASE
 NOTE THAT MANY SHEETS ARE MISSING SEAL.
 471.025 FS/FAC.
 2) PAGE A4.0, BAR ELEVATION (8) PLEASE
 COMPLY WITH FACBC-97 SEC 4.24. PROVIDE
 DETAILS ON PLANS.
 3) PAGE A4.0 MENS RESTROOM (6) (11).
 PLEASE COMPLY WITH FACBC-97 SEC 4.18 &
 4.22.5
 4) PAGE P1.0 WATER HEATER TO BE READILY
 ACCESSIBLE PER SPC-94 SEC 501.7. PLEASE
 PROVIDE A PERMINATE SHIPS LADDER AND A
 WORKING PLATFORM FOR SERVICING, MINIMUM
 30" X 30".
 5) PAGE P2.0 SANITARY ISOMETRIC. MENS
 ROOM URNAL AND ELECT. WATER COOLER CAN
 NOT DRAIN TO STACK ON A CROSS. PLEASE
 HAVE FIXTURES DRAIN TO STACK AT DIFFER-
 ENT HEIGHTS.
 6) PAGE P2.0 WATER ISOMETRIC AIR CHAMB-
 ERS TO COMPLY WITH SPC-94 SEC 607.8.3,
 (ACCESSIBLE AND RECHARGABLE) PER WH-PDI
 201. IF WATER HAMMER ARRESTORS ARE USED,
 THEY SHALL COMPLY WITH MANUFACTURES IN-
 STALLATION INSTRUCTIONS FOR SIZING AND
 LOCATION AND WH-PDI 201 NOT AT TOP OF
 DROP. SHOW DETAILS ON ISO. ALSO SHOW
 SHUT OFF VALVES FOR ALL HOSE BIBBS.
 7) PAGES A4.0 & P1.0 DRINKING FOUNTAIN.'
 PLEASE COMPLY WITH FACBC-97 SEC 5.15 AND
 SEC 4.1.3(10)(A) FOR THOSE WHO HAVE TRO-
 BLE BENDING OR STOOPING.
 8) PAGE P3.0 GENERAL NOTES #16. SEE NOTE
 COMMENT #6 ABOVE.
 9) PLEASE PROVIDE CALCULATIONS FOR MIN-
 IMUM FACILITIES FOR FIXTURES. USE SPC-94
 TABLE 407.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377