| Date |
Text |
| 2001-10-03 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 |
| | 1) PLEASE NOTE THAT ALL PLANS SUBMITTED |
| | BY AN ENGINEER ARE TO BE SIGNED, DATED, |
| | AND SEALED BY PERSON OF RECORD. PLEASE |
| | NOTE THAT MANY SHEETS ARE MISSING SEAL. |
| | 471.025 FS/FAC. |
| | 2) PAGE A4.0, BAR ELEVATION (8) PLEASE |
| | COMPLY WITH FACBC-97 SEC 4.24. PROVIDE |
| | DETAILS ON PLANS. |
| | 3) PAGE A4.0 MENS RESTROOM (6) (11). |
| | PLEASE COMPLY WITH FACBC-97 SEC 4.18 & |
| | 4.22.5 |
| | 4) PAGE P1.0 WATER HEATER TO BE READILY |
| | ACCESSIBLE PER SPC-94 SEC 501.7. PLEASE |
| | PROVIDE A PERMINATE SHIPS LADDER AND A |
| | WORKING PLATFORM FOR SERVICING, MINIMUM |
| | 30" X 30". |
| | 5) PAGE P2.0 SANITARY ISOMETRIC. MENS |
| | ROOM URNAL AND ELECT. WATER COOLER CAN |
| | NOT DRAIN TO STACK ON A CROSS. PLEASE |
| | HAVE FIXTURES DRAIN TO STACK AT DIFFER- |
| | ENT HEIGHTS. |
| | 6) PAGE P2.0 WATER ISOMETRIC AIR CHAMB- |
| | ERS TO COMPLY WITH SPC-94 SEC 607.8.3, |
| | (ACCESSIBLE AND RECHARGABLE) PER WH-PDI |
| | 201. IF WATER HAMMER ARRESTORS ARE USED, |
| | THEY SHALL COMPLY WITH MANUFACTURES IN- |
| | STALLATION INSTRUCTIONS FOR SIZING AND |
| | LOCATION AND WH-PDI 201 NOT AT TOP OF |
| | DROP. SHOW DETAILS ON ISO. ALSO SHOW |
| | SHUT OFF VALVES FOR ALL HOSE BIBBS. |
| | 7) PAGES A4.0 & P1.0 DRINKING FOUNTAIN.' |
| | PLEASE COMPLY WITH FACBC-97 SEC 5.15 AND |
| | SEC 4.1.3(10)(A) FOR THOSE WHO HAVE TRO- |
| | BLE BENDING OR STOOPING. |
| | 8) PAGE P3.0 GENERAL NOTES #16. SEE NOTE |
| | COMMENT #6 ABOVE. |
| | 9) PLEASE PROVIDE CALCULATIONS FOR MIN- |
| | IMUM FACILITIES FOR FIXTURES. USE SPC-94 |
| | TABLE 407. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT. 8377 |