Plan Review Notes
Plan Review Notes For Permit 01090187
Permit Number 01090187
Review Stop E
Sequence Number 1
Notes
Date Text
2001-09-18 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT NO LOAD CALCU-
 -LATIONS WERE SUBMITTED. PLEASE ALSO
 NOTE THAT ALL CONTINUOUS LOADS ARE TO
 BE SHOWN AT 125%. 215-5/220-3 CONTIN,
 PER 230-42 AND 215-2/3
  
 2)NOTE: PLEASE NOTE THAT ALL PLANS DONE
 BY AN ARCH/ENGINEER ARE TO BE SIGNED,
 DATED AND SEALED BY PERSON OF RECORD.
 PLEASE NOTE THAT MANY PLANS ARE MISSING
 SEAL. 481.221 AND 471.025.FS/FAC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372