| 2001-09-18 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT NO LOAD CALCU- | | | -LATIONS WERE SUBMITTED. PLEASE ALSO | | | NOTE THAT ALL CONTINUOUS LOADS ARE TO | | | BE SHOWN AT 125%. 215-5/220-3 CONTIN, | | | PER 230-42 AND 215-2/3 | | | | | | 2)NOTE: PLEASE NOTE THAT ALL PLANS DONE | | | BY AN ARCH/ENGINEER ARE TO BE SIGNED, | | | DATED AND SEALED BY PERSON OF RECORD. | | | PLEASE NOTE THAT MANY PLANS ARE MISSING | | | SEAL. 481.221 AND 471.025.FS/FAC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|