| 2001-09-19 00:00:00 | BUILDING PLAN REVIEW |
| | 01090187 |
| | 3400 CELEBRATION BLVD |
| | CLUBHOUSE (R-3) |
| | CONT: GERARD GROUP INC |
| | TEL: (954) 383-2652 |
| | FAX: (561) 795-4060 |
| | |
| | SBC= 1997 STANDARD BUILDING CODE |
| | SBC*= COUNTYWIDE AMENDMENTS 1997 |
| | STANDARD BUILDING CODE |
| | |
| | 1)- PLANS ARE TO BE SUBMITTED UNDER (2) |
| | INDEPENDENT PLAN REVIEWS: |
| | 3400 CELEBRATION BLVD CLUBHOUSE $250.00 |
| | 3420 CELEBRATION BLVD GATEHOUSE $250.00 |
| | |
| | 2)- SBC*104.2.2 ADDITIONAL INFORMATION |
| | REQUIRED, A SUREY SIGNED SEALED & DATED |
| | |
| | 3)- A PLOT PLAN THAT SHOWS LOCATION OF |
| | STRUCTURE AND PROPERTY LINES(SURVEY WILL |
| | WORK IF PROPOSED BUILDING IS LOCATED ON |
| | SURVEY). |
| | |
| | 4)- FL. ENERGY CODE FOR EACH BUILDING. |
| | UNLESS NO AIR FOR THE GATEHOUSE. |
| | |
| | 5)- SHEET A1.0 DOESN'T SHOW CHANGE IN |
| | GRADE, SHEET S-1 DOES DEPICT (2) 4" |
| | CHANGES IN GRADE. THE FAIR HOUSING ACT |
| | REFRENCES THE ANSI STANDARDS,SEE 303.2 |
| | FOR CHANGE IN GRADE(VERTICAL).ACCESSIBLE |
| | ROUTES ANSI 402.2. |
| | |
| | 6)- MISSING ARE (2) COPIES OF THE SOILS |
| | REPORT GIVING THE MINIMUM BEARING VALUE. |
| | SBC* 1804.2.7.2 |
| | |
| | 7)- SBC 1606.2.6.2 COMPONENTS & CLADDING |
| | THE CITY REQUIRES (2) PRODUCT TESTING RE |
| | PORTS, FOR THE EXTERIOR ENVELOPE OF THE |
| | BUILDING, THESE ARE THE ITEMS REQUIRING |
| | PRODUCT TESTING: |
| | A- EXTERIOR DOORS * |
| | B- SLIDING DOORS* |
| | C- GARAGE DOORS(OVERHEAD)* |
| | D- WINDOWS* |
| | E- SKYLIGHTS* |
| | F- ROOFING ASSEMBLIES |
| | *- GLAZED OPENINGS WILL REQUIRE |
| | STORM SHUTTERS IF OPENINGS DO NOT |
| | MEET THE REQUIREMENT FOR LARGE |
| | MISSLE RESISTANCE TESTING. A SEPER- |
| | ATE PERMIT WILL BE REQUIRED IF NOT |
| | PART OF THE BUILDING PERMIT PACKAGE |
| | ALSO READ THE CITIES OFFICIAL |
| | INTERPRETATION ON POLICIES, NOTE |
| | ITEMS 14 & 15. SEE THE REQUIREMENTS |
| | FOR THE INSTALATION SCHEDULE & KEY |
| | PLAN. COPY ATTACHED. |
| | |
| | 8)- S-3-3 ROOF SYSTEMS BETWEEN THE FLAT |
| | & PITCHED ROOFING SYSTEMS, SBC |
| | 1507.3.1.5. FLASHING & COUTERFLASHING AT |
| | WALL ABUTMENTS. PLEASE PROVIDE DETAILS. |
| | SBC 1507.3.1.6. WHEN CRICKETS REQUIRED. |
| | |
| | 9)- S3-3 THIS SAME DETAIL SHOWS TRUSSES |
| | INSET IN THE MASONARY WALL, CHECK CLEAR- |
| | ENCES PLUS SHEET S1 INDICATES THE |
| | TRUSSES AND FILLED VERTICAL CELLS IN THE |
| | SAME SPACE???? |
| | |
| | 10)- SHEET S-2 STEEL COLUMN SCHEDULE: |
| | J-BOLT ANCHOR LENGTH NOT GIVEN. |
| | |
| | 11)- FL ACCESSIBILITY CODE 4.6 PARKING |
| | AND PASSENGER LOADING ZONES. |
| | |
| | 12)- FL ACCESSIBILITY CODE 4.5 GROUND & |
| | FLOOR SURFACES ALONG ACCESSIBLE ROUTES |
| | AND IN ACCESSIBLE ROOMS AND SPACES INCLU |
| | DING FLOORS, WALKS, STAIRS, RAMPS & |
| | CURB RAMPS SHALL BE STABLE, FIRM, SLIP- |
| | RESISTANT. ADDAGG A4.5 A STATIC COEFFICI |
| | ENT OF FRICTION OF 0.6 IS RECOMMENDED |
| | FOR ACCESSIBLE ROUTES AND 0.8 FOR RAMPS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096X8412 |