| Plan Review Notes For Permit 01090052 |
| Permit Number |
01090052 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2002-01-31 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHT P-2 WATER RISER DIAGRAM, AIR | | | CHAMBER DETAIL NOT SHOWN AS REQUSTED IN | | | LAST REVIEW. SEE SHEET PROVIDED AND GIVE | | | DETAILS ON PLANS FOR VALVES IN AIR | | | CHAMBERS. | | | 2) SHT P-2 PREVIOUS COMMENTS NOT ADDRESS | | | ED PROPERLY. VENT FOR DOUBLE LAV IS | | | STILL GOING UP AND THEN BACK DOWN. THIS | | | IS NOT ACCEPTABLE. | | | 3) SHT P-2 WATER HEATER EMERGENCY PAN | | | DRAIN SHALL BE 1" NOT 3/4" AS SHOWN. | | | SPC SEC 507.8.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|