Plan Review Notes
Plan Review Notes For Permit 01090052
Permit Number 01090052
Review Stop P
Sequence Number 3
Notes
Date Text
2002-01-07 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PER PREVIOUS REVIEW SHT P-2 AIR
 CHAMBERS SHALL BE ACCESSIBLE AND RECHARG
 EABLE PER WH-PDI 201 SPC SEC 607.8.3.
 SEE ATTACHED SHEET FOR APPROVED AIR
 CHAMBERS. SHOW DETAIL ON PLANS IF USING
 AIR CHAMBERS.
  
 2) PER PREVIOUS REVIEW SHT P-2 VENT NOT
 APPROVED. VENT FOR DOUBLE LAV IN WOMENS
 RESTROOM RISES AND THEN DROPS DOWN INTO
 VENT HEADER. THIS IS NOT A LEGAL VENT.
  
 3) PER PREVIOUS REVIEW SHT P-2 PAN DRAIN
 NOT SHOWN. PLUMBING NOTES #27 NOT APPRO-
 VED. SPC SEC 507.8.3 - 507.8.4 RELIEF
 LINE AND PAN DRAIN LINE TO BE PIPED FULL
 SIZE SEPARATELY AND TERMINATE NO LESS
 THAN 6" ABOVE GROUND.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377