| Plan Review Notes For Permit 01090052 |
| Permit Number |
01090052 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-12-13 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE TAPPING A TAP FROM | | | MAIN GUTTER TO OTHER GUTTER. 240-21 | | | | | | 2)NOTE: PLEASE NOTE SIZECONDUCTORS | | | IN MAIN GUTTER IS NOT SHOWN. | | | | | | 3)NOTE: PLEASE STILL NEED TO CLARIFY | | | HOW CONDUCTORSARE COMING IN FROM | | | OUTSIDE? ROOM TENDS TO SIT BACK IN FROM | | | OUTSIDE WALL AND NO MORE THAN 8' OF UN- | | | -PROTECTEDPER LOCAL AMENDMENTS. | | | | | | 4)NOTE: PLEASE NOTE THE SIZE OF GROUND- | | | -ING ELECTRODE CONDUCTOR PER 250-66 | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|