2001-12-13 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE TAPPING A TAP FROM
 MAIN GUTTER TO OTHER GUTTER. 240-21
  
 2)NOTE: PLEASE NOTE SIZECONDUCTORS
 IN MAIN GUTTER IS NOT SHOWN.
  
 3)NOTE: PLEASE STILL NEED TO CLARIFY
 HOW CONDUCTORSARE COMING IN FROM
 OUTSIDE? ROOM TENDS TO SIT BACK IN FROM
 OUTSIDE WALL AND NO MORE THAN 8' OF UN-
 -PROTECTEDPER LOCAL AMENDMENTS.
  
 4)NOTE: PLEASE NOTE THE SIZE OF GROUND-
 -ING ELECTRODE CONDUCTOR PER 250-66
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  