| Plan Review Notes For Permit 01090052 |
| Permit Number |
01090052 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-11-13 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PAGE P-2, SANT RISER DIAGRAM. URNAL | | | SHALL BE WALL MOUNT NOT FLOOR MOUNT AS | | | SHOWN ON RISER. DRINKING FOUNTAIN SHOWN | | | ON MENS SIDE OF ALCOVE ON FLOOR PLAN AND | | | ON WOMENS SIDE ON RISER. PLEASE CLARIFY. | | | 2) PAGE P-2, WATER RISER DIAGRAM. DOUBLE | | | LAV SHOWN IN MENS ROOM AND DRINKING | | | FOUNTAIN SHOWN ON WOMENS SIDE. AIR CHAM- | | | BERS ARE QUICK FIX AND REQUIRE ACCESS & | | | SHALL BE RECHARGEABLE PER SPC SEC 607.8. | | | 3. AND PER PDI-WH 201. IF WATER HAMMER | | | ARRESTORS ARE USED THEY SHALL BE SIZED & | | | LOCATED PER MANUFACTURE INSTALLATION IN- | | | STRUCTIONS AND PDI-WH 201. NOT LOCATED | | | ON TOP OF DROP AS SHOWN. | | | 4) PAGE P-2 VENT ON SANT. RISER DIAGRAM | | | SHALL NOT GO UP - OVER - & DOWN AS SHOWN | | | FOR LAV IN WOMENS ROOM. | | | 5) PAGE P-2 PLEASE INDICATE WHERE AND | | | HOW THE PAN DRAIN AND T&P TERMINATE FROM | | | WATER HEATER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|